EQUIPMENT / EQUIPMENT FAMILY

Hanyan commercial inverter modular heat pumps

The detailed family page adds a −12°C capacity basis and three-phase supply; module count still needs a matched winter-duty selection.

From Hebei Hanyan Refrigeration Equipment Co., Ltd.

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Commercial inverter modular air-source heating and cooling family
Manufacturer catalogue image · Commercial inverter modular family
01 / UNDERSTAND THE EQUIPMENT

Use the commercial family’s own specifications to select a modular plant

Hanyan publishes commercial inverter heating/cooling equipment that can be combined in up to sixteen modules. The detailed product page adds a single-unit heating range of 20–108 kW at −12°C ambient, a 380V 3N~50Hz supply and a stated −30°C to 45°C operating range. Those specifications belong to this reviewed commercial family, rather than being copied from adjacent household or hot-water cards.

The publication does not map the capacities to complete model codes or provide the entering/leaving water temperatures, flow, input power or defrost conditions behind them. The bottom of the operating range is not a full-capacity or efficiency guarantee at that temperature.

Treat this as a family reference for an enquiry. The supplier must return the selected modules and their output at the actual winter water duty, together with the plant controls, auxiliaries and delivery/support scope.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
Commercial inverter modular family

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Published single-unit heating range20–108 kW at −12°C ambientManufacturer family range at the stated ambient. No full model mapping, water-temperature basis or power schedule is published in the reviewed text. Source
Published electrical supply380V 3N~50HzOriginal supply notation from this family page; selected-unit current, protection and wiring requirements still need a schedule. Source
Published operating range−30°C to 45°CManufacturer operating-range statement, not a capacity curve, COP guarantee or rated output at either endpoint. Source
Published modular arrangementUp to 16 modulesCombination statement, not proof of compatible model mixing, sixteen-module output or guaranteed redundancy. Source
Published refrigerant and compressor descriptionR410A; Copeland ZW-series high-temperature-water compressor; vapour-injection systemManufacturer family description. Exact compressor designation, refrigerant charge and maximum water temperature are not identified. Source

Selection and application review

Separate inverter heating from the nearby product families

The homepage lists fixed-speed commercial heating, household heating, hot-water, pool and drying products separately. A shared brand or refrigerant does not make their duty schedules interchangeable.

Commercial inverter heating/cooling

Use this detail page’s 20–108 kW at −12°C, stated operating range and modular description, with the missing water conditions explicitly requested.

Read the source

Commercial fixed-speed or hot-water equipment

The homepage presents these as different families. Do not assume their control behavior or 60°C hot-water wording is part of the selected inverter heating/cooling model.

Read the source

Calculate module quantity from the requested winter duty

Provide the building load curve, winter design ambient, required supply/return-water temperatures, flow and daily operating pattern. Request the output and electrical demand of the proposed model at those conditions, including the supplier’s defrost and low-ambient selection assumptions.

The family’s upper 108 kW number is not identified as the output of every module. Multiplying it by sixteen would not establish a plant capacity at the project’s duty. Ask the supplier to identify the compatible modules, control arrangement and the capacity remaining in the agreed unavailable-unit scenario.

For cooling, request a separate selected-duty schedule. The page says the equipment handles cooling and heating but does not publish a numerical cooling rating or cooling-mode operating map.

Match the electrical and water-side plant to the actual offer

The published three-phase supply is useful for an initial feasibility discussion, but it is not a circuit-design schedule. Obtain maximum running/start current, selected protection and cable requirements, compressor/drive arrangement and the full equipment electrical scope from the responsible supplier and designer.

Request water flow and pressure drop, allowable water conditions, connection sizes and proposed pumps, buffer/separation arrangement, controls and freeze-protection responsibilities. These are enquiry questions, not installation settings or a requirement to use a particular hydraulic layout.

Submit the proposed site layout, service access and outdoor-air constraints. The page’s large-airflow/low-noise wording has no measured airflow or acoustic figure, so obtain the actual selected-unit air and noise data for a location-sensitive project.

A low-temperature statement is not a water-temperature or savings guarantee

The detailed page expressly describes −30°C operation and a vapour-injection arrangement for this commercial family. It supplies no capacity/power curve at −30°C, so no COP or annual saving is asserted here.

Its high-temperature-water compressor description does not state a maximum outlet-water temperature. The homepage’s 60°C claims appear beside other product families and are not assigned to this selection.

Likewise, the R410A description does not establish suitability under the destination’s current rules or the delivered charge. Require the supplier and responsible designer to confirm the exact refrigerant configuration and applicable project requirements; no destination-specific legal conclusion is made.

Ask for one model-specific selection and availability confirmation

The current public text is a family description, not a complete orderable schedule. Request the full code/revision, heating and cooling capacities at your conditions, power and flow data, modulation/defrost behavior, module compatibility, dimensions and acoustic data.

Separately confirm the current supplying entity, production location, availability, commissioning and support. A live catalogue does not establish current production or a delivery slot. The manufacturer-profile review has a pending historical public-record check; no present operating-status conclusion or shipment promise is made here.

Agree the performance/acceptance basis, auxiliaries, installation responsibilities, current manuals, conformity records and warranty in the offer. A household-unit manual shown elsewhere on the website is not a substitute for the selected commercial modular equipment’s manual.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Hanyan commercial inverter modular product detailChecked 2026-10-11 · Full detail read: 20–108 kW at −12°C ambient, original supply notation, operating range, compressor/refrigerant and sixteen-module statement; incomplete rating basis preserved.
  2. Official homepage family divisionsChecked 2026-10-11 · Commercial inverter, fixed-speed and other application families distinguished; adjacent 60°C statements not transferred.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Continue the selection