Review the commercial entity, Chenzhou manufacturing claim and the exact refrigeration package together; the displayed certificates name a different company.
1 published equipment referenceLatest source review 2026-10-11
01 / COMPANY
What this manufacturer offers
The DKenergy website identifies its operator as 金星工业(广东)有限公司, Jinxing Industrial (Guangdong) Co., Ltd. Its contact address is an office in Huizhou: Room 05, Floor 11, Unit 2, Building B, Kaisa Centre Phase II, 11 Huizhou Avenue, Huicheng District. The image-led company introduction separately describes a production base in Beihu District, Chenzhou.
The public catalogue includes refrigeration condensing units and several air-conditioning/chiller categories. For the CFMZ MINI family, there is useful construction and compressor information, but no model-by-model capacity schedule or complete selection envelope.
A material qualification issue is visible in the official certificate gallery: the three management-system certificates inspected name 依科莱文(郴州)智能控制系统集成有限公司 rather than Jinxing. The reviewed pages do not document the legal relationship or establish that the certificate scopes cover Jinxing and the offered manufacturing site. Keep the contracting company, production company and certificate holder separate until the supplier provides that evidence.
Site operator
金星工业(广东)有限公司 / DKenergyName used by the official site header and contact page; no independently obtained current company-register extract. Source
Published commercial contact
Huicheng District, Huizhou, GuangdongThe specific Kaisa Centre office address is a contact location, not proof of a production line. Source
Production-base claim
Beihu District, Chenzhou, HunanSupplier introduction and factory gallery; actual operating capacity and legal site operator not audited. Source
Certificate-holder distinction
依科莱文(郴州)智能控制系统集成有限公司Actual quality, environmental and occupational-health management images name this different entity. No transfer of certification to Jinxing. Source
Reviewed refrigeration family
CFMZ-002–006M/EM, published 2–6 HPCompressor-class family headline; not a cooling-capacity rating. Source
Swipe the table, or focus it and use arrow keys, to read conditions and sources.
Manufacturer-published information · CFMZ-002–006M/EM
Parameter
Published value
Conditions and evidence
Published family
CFMZ-002–006M/EM · 2–6 HP
No individual compressor/cooling-duty schedule; HP must not be presented as delivered cooling kW. Source
Printed cabinet envelope
1030(L) × 410(W) × 850–1250(H)
The page does not state a unit or map each height to a model. Obtain the selected dimensioned drawing. Source
Compressor wording
Heading: ZB; body: ZB and ZSI, with other-brand options
Exact compressor part number, configuration and approved operating envelope remain to be specified. Source
Refrigerant wording
R134a · R404A · R57 · R22 as printed
R57 is an unresolved source designation; no automatic correction or universal compatibility claim. Source
03 / PROJECT REVIEW
Qualify the supplier behind DKenergy before approving the refrigeration package
Resolve the commercial and manufacturing chain first
The company introduction is presented as an image. It describes a 2019 establishment, a Huizhou headquarters and a Chenzhou production base, and states an origin connected to a Korean company. These are supplier statements; the reviewed material contains no independently authenticated corporate-history or ownership record.
For an order, request the registered supplier name, invoice/export entity, manufacturing-site operator and their relationship. Ask which company designs, assembles, tests and warrants the selected condensing unit. A shared brand, office address or certificate gallery does not by itself establish those responsibilities.
Huizhou contact entity
Use the full Jinxing name on the supplier offer and verify the contracting/export responsibilities.
The certificate images are useful evidence of scope, not interchangeable credentials
The three actual displayed images concern quality, environmental and occupational-health/safety management systems. Their stated activities concern refrigeration/air-conditioning technology development, assembly, sales and technical services. Their named holder differs from the site operator.
This review therefore does not describe Jinxing as ISO-certified. Request full-resolution originals and issuer verification, with the certificate holder, site addresses, scope and current status. If a connected manufacturing entity performs the work, document that chain in the contract and inspection plan. Management-system certification still does not supply CFMZ cooling performance, electrical conformity or a refrigerant approval.
What the gallery establishes
Three management-system images are displayed with a different named holder; the actual images were inspected.
The legal relationship, coverage of the selected site/entity, current status and order-specific product documents.
Review the production claims without turning the photographs into an audit
The introduction claims a base occupying 150 mu with 60,000 square metres of modern buildings. Homepage counters use other broad scale headlines, including 100 employees and a 5,000 facility figure without a clear basis matching the introduction. The figures do not form a coherent audited current-capacity schedule.
The factory gallery shows office/factory/park imagery; an exterior photograph cannot prove installed lines, test benches or spare capacity for this unit. Request a current site layout, assembly/test capability and planned production slot for the selected quantity. Published visits and news photographs should not be treated as government endorsement or delivered-unit acceptance.
Treat CFMZ as a configuration enquiry, not a finished cold-store design
The reviewed CFMZ MINI page lists CFMZ-002–006M/EM and 2–6 HP. Its heading emphasises ZB, while the text mentions both ZB and ZSI scroll compressors and other compressor-brand options. It associates ZB with medium/high-temperature conditions and ZSI with low-temperature service, but gives no exact compressor part numbers or unit capacity table.
Provide storage/process temperature, heat load, design outdoor conditions, refrigerant and evaporator requirements. Ask for the offered compressor model, unit selection at those conditions and an explicit control/protection bill of materials. The cabinet photograph and HP band cannot establish refrigeration output or compatibility with an existing evaporator.
Separate construction statements from measured operating performance
The source describes internally grooved copper tubes with V-wave aluminium fins, galvanised and coated steel, flare connections and inlet/outlet stop valves. It claims quiet construction, salt-spray durability and installation time reduced by 50%. No measured sound level, corrosion-test method/duration/report or timed installation comparison accompanies those statements.
The refrigerant text prints R134a, R404A, R57 and R22. R57 is retained as an unresolved published designation, not silently rewritten to R507. Require the exact refrigerant, compressor/oil compatibility and applicable destination requirements in the written selection. Agree condenser cleaning access, ambient operation and required wall clearances rather than assuming that near-wall wording authorises zero-clearance mounting.
Define handover, protection and service responsibilities in the offer
The reviewed pages do not establish a fixed MOQ, lead time, price or detailed warranty duration. Ask whether the supply includes a controller, receiver and protective devices, and identify items supplied by the refrigeration installer. Confirm pressure/leak/electrical checks and traceable results for the shipped configuration.
For an overseas project, specify commissioning documentation, spare parts, technical support, warranty start/event and exclusions. Agree who remedies a compressor/control issue and who pays removal, labour, refrigerant and transport costs. Those responsibilities should follow the confirmed supplier/manufacturer chain rather than a general brand headline.
Verify the entities
Approve the contract/export name, actual manufacturing site and applicable certificate evidence.
Review configuration-specific tests, identification, commissioning instructions, spares and written warranty/service terms.
07 / TRANSPARENCY
Sources and review scope
Compiled by HVACDeck Editorial. Page review: 2026-10-11. Publications are attributed below; their statements are not independent measurements by this platform.
Official contact and site operatorChecked 2026-10-11 · Actual address/entity read; existing private CRM375 email/source fields preserved.
Official image-led company introductionChecked 2026-10-11 · Actual introduction image inspected; supplier history/base/scale statements are not an independent audit.