Air-side assembly
Which mixing, filter, coil, heating, humidity, recovery and fan sections are included, in what order?
A sectional air-handler publication under a DX title: define the actual coil, refrigeration package and air-treatment duty before comparing offers.
From Jiangsu Hanwei Air Conditioning and Refrigeration Equipment Co., Ltd.
Individual product research · HVACDeck Editorial · Sources checked 2026-10-11
Hanwei’s actual product-item-27 page is titled 直膨式空气处理机组, but its detailed text describes a combined sectional air handler, including water-resistance language and coil-header drain/vent valves. It publishes a broad 2,000–200,000 m³/h design airflow range and selectable air-treatment sections. That is not an exact DX model rating or proof that a complete refrigeration package is included.
The actual main image depicts a sectional cabinet beside an outdoor-style unit. Two detail photographs show cabinet doors, gauges/sight ports and a controls panel. None provides a readable numerical model schedule or refrigerant-circuit diagram. Use the publication as a construction and enquiry reference, while requiring an explicit selected-system drawing and technical schedule.
This is an equipment family; its range does not identify one orderable configuration.
Swipe the table, or focus it and use arrow keys, to read the conditions and sources.
| Parameter | Published value | Conditions and evidence |
|---|---|---|
| Published airflow range | 2,000–200,000 m³/h | Combined-air-handler range in the DX-titled description; not a selected unit duty. Source |
| Selectable sections | Mixing, cooling, heating, filtration, humidification, attenuation, recovery, fan and flow equalisation | Catalogue choices; section inclusion/order and final size require an approved selection. Source |
| Fan description | Forward- or backward-curved double-inlet centrifugal fan | Supplier says impeller/pulley balancing; no selected curve, drive or acoustic rating. Source |
| Drain construction | Sloped insulated condensate pan; coil header drain and vent valves | Construction text includes water-side features; exact DX coil/package remains to be confirmed. Source |
| Casing description | Colour-coated steel exterior and aluminium-profile frame | No casing leakage, thermal-bridge or insulation classification published on the item. Source |
A sectional air handler describes the air path and cabinet; direct expansion describes a refrigerant evaporator arrangement. The page’s heading, water-side text and illustration do not settle what will be delivered. Ask the supplier to mark the selected coil type and refrigeration components on a current system drawing.
Which mixing, filter, coil, heating, humidity, recovery and fan sections are included, in what order?
Which outdoor/compressor unit, refrigerant circuits, expansion/control devices and operating modes match this coil?
Who supplies piping, insulation, electrical protection, drainage and commissioning, with what installation limits?
Specify outdoor and return-air quantities, entering dry-bulb/humidity conditions, required supply-air condition and room/process load. For a moisture-sensitive application, state the absolute moisture or dew-point target and the moisture entering the process. A nominal cooling capacity cannot alone prove humidity control.
Ask for total and sensible cooling, moisture removal and leaving-air conditions at the agreed mix and airflow. Identify any reheat, humidification or desiccant stage separately. The catalogue offers several section types; it does not give this unit’s latent capacity, leaving dew point or a quantified control tolerance. Do not transfer figures from Hanwei’s separate rotary or liquid-desiccant equipment.
Provide required external static pressure and account for the selected internal filters, coils, recovery and attenuation sections. Confirm whether the quoted pressure is external, fan static or total, and which filter condition is used. The broad airflow range has no accompanying pressure schedule.
Review the actual fan curve, operating point, speed/drive and motor input with air density and test basis. Check clean and loaded-filter operation and any permitted speed control. A balanced impeller/pulley statement does not establish acoustic performance or stable operation at every flow. The forward- and backward-curved alternatives require separate selections rather than a single assumed efficiency.
The supplier describes a sloped insulated pan and inspection doors. For the selected fan/coil arrangement, establish the pressure at the drain, trap design, drain fall and service access with the responsible installer. A sloped tray alone does not prove it will drain under operating pressure. Check the actual arrangement during commissioning.
Obtain casing dimensions, delivery-section splits and connection/support details. Reserve space for filter and coil removal, door opening and fan/drive maintenance. Confirm lifting and plantroom access before ordering a large sectional assembly; a photograph showing doors does not establish sufficient space at the buyer’s site.
The page describes colour-coated steel, aluminium framing and air-tight inspection doors but gives no measured leakage, thermal or corrosion classification. Request the selected panel/insulation construction and relevant test evidence if the project requires defined classes. Agree filter grades and sizes through the actual project specification, not the broad “initial/medium/high-efficiency” wording alone.
Hanwei offers customised automatic controls without a sequence or interface schedule. Require sensor locations, temperature/humidity control, fan and refrigeration interlocks, condensate/freeze protection and fault handling appropriate to the selected package. Confirm communication protocols and control responsibility rather than infer integration from a photographed display.
The publication establishes no fixed model price, lead time or warranty. Compare quotations against the same air-process and supply boundary, so a water-coil cabinet, a DX indoor assembly and a complete matched system are not treated as equivalent offers.
Issue airflow/pressure, entering/leaving conditions, moisture duty, selected sections, utilities and site constraints.
Approve exact coil/refrigeration arrangement, fan selection, dimensions/access, casing/filter construction and control sequence.
Verify air quantity, pressure, temperature/humidity and drainage at agreed conditions; hand over selection reports, controls and maintenance instructions.
Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.
Editorial method and corrections · Report a detail with this page URL
Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.