EQUIPMENT / EQUIPMENT FAMILY

Langri air-source heating/cooling units · Ratings and cold-weather evidence

Convert P labels and outdoor-casing pictures into a named selection at the actual weather, water and electrical conditions.

From Hebei Langri · Fan-coil manufacture and heating/cooling equipment

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Langri air-source heating/cooling units · Ratings and cold-weather evidence
Manufacturer catalogue image · Domestic/commercial air-source heating-cooling family
01 / UNDERSTAND THE EQUIPMENT

Select winter duty without inventing a low-temperature rating

Langri offers air-source variable-frequency heating/cooling equipment in domestic and commercial catalogue sections. Its reviewed 3P illustration shows a compact side-fan outdoor casing with the 筑立方 brand, while the commercial image shows a tall twin-top-fan arrangement. The domestic recommendations include 5–6P and 8–10P; the commercial detail groups 15P, 25P, 30P, 50P and 60P in one offer. These are supplier size labels, not verified kW output at an identified air/water condition.

The size labels are consolidated into one heating/cooling family. No separate capacity URLs or manufactured performance table has been created. Important uncertainties remain: the current refrigerant/circuit, selected heating output in cold weather, defrost behaviour, water-side connections and complete electrical input. The company describes a −35°C enthalpy laboratory, but that does not rate these pictured units at −35°C. Two displayed heat-pump CCC originals expired in May 2025 and cannot establish current conformity for this offer.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
Domestic/commercial air-source heating-cooling family

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Official scopeDomestic/commercial variable-frequency air-source heating and coolingTwo actual product details read; current ordered circuit not disclosed. Source
Compact pictured arrangement3P labelled side-fan outdoor casingOriginal illustration; no kW rating or room-area capacity supplied. Source
Commercial pictured arrangementTall enclosure with two top fans; grouped 15P–60P labelsImage and title read; size alternatives consolidated rather than separate URLs. Source
Low-temperature lab statementCompany describes a −35°C enthalpy laboratoryNot a selected-unit capacity/COP/defrost result at −35°C. Source
Historical heat-pump certificate boundaryTwo displayed CCC originals valid to 9 May 2025Expired at review; printed R410A/voltage details cannot automatically describe current pictures. Source
Missing operating mapHeating/cooling output, complete input, air/water conditions and defrost basisNo COP, efficiency grade, minimum ambient or freeze-protection guarantee inferred. Source

Selection and application review

Request the design-day heating selection

Provide the design outdoor conditions, required leaving/return water temperatures, building or process heat demand and operating profile. Ask for a named model's heating output and complete input at those simultaneous conditions, with the supplier's defrost and auxiliary-heating treatment stated. A 3P or 60P label cannot settle that selection.

The company claims a laboratory with a −35°C capability. Ask for the selected unit's original test report and operating envelope rather than turning a laboratory endpoint into a guaranteed minimum ambient. Require the behaviour at the actual lowest weather and the written backup strategy if the heat pump cannot maintain the required duty.

Match the water circuit and summer duty

The reviewed casing images do not identify load connections, pump/buffer inclusion or minimum water volume/flow. Obtain the circuit diagram and selected pressure-drop data. Clarify which hydraulic parts, isolation, controls and treatment responsibility sit inside the quote and which are installed at the building.

For cooling, require the rated output at actual entering/leaving water and outdoor conditions. Coordinate with the selected fan coils, including their water temperatures and controls. Do not assume that a domestic P label, a terminal photograph and a commercial casing form a pre-engineered matched system.

Resolve outdoor airflow, defrost drainage and power

The compact side-fan and commercial top-fan illustrations show different external airflow arrangements. Request the exact clearance, support and service instructions for the selected unit. Site drawings should identify the discharge path and other outdoor equipment, with the manufacturer's accepted layout. Neither picture establishes sound at a neighbouring property or at an occupied façade.

Agree the defrost-water drainage arrangement and freeze-protection procedure required by the selected manufacturer instructions. Obtain complete electrical loads, supply, starting/drive requirements and protective/control details. Historical certificate voltages and refrigerant entries should not be copied into a new specification until the current model is confirmed.

Close conformity and control scope before purchase

Both inspected CCC originals show issue on 9 May 2020 and expiry on 9 May 2025. They identify specific historical heat-pump schedules. Obtain the current document and relevant model annex where required, together with current issuer status; do not use these expired images as live compliance proof.

Request the selected controller's plant/terminal interlock, local protections, fault reporting and restart sequence. The variable-frequency name does not establish a communication protocol or a measured seasonal result. Compare quotations using the same cold-weather and summer duty, complete input, included hydraulic/electrical equipment and agreed acceptance evidence. Current price, measured site savings and independently verified efficiency remain unknown.

  1. Issue weather and water duty

    State design-day heating and summer cooling conditions with actual terminal/load needs.

  2. Obtain a current model dossier

    Require operating maps, defrost/backup treatment, circuit/electrical schedules and conformity scope.

  3. Approve the installed system

    Agree outdoor layout, drainage, controls and tests for the complete quoted package.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official domestic 3P heating/cooling detailChecked 2026-10-11 · Complete page and original side-fan image reviewed; P labels have no published thermal conditions.
  2. Official grouped commercial heating/cooling detailChecked 2026-10-11 · Complete page, grouped labels and original twin-top-fan image read; no quantified duty map supplied.
  3. Official company laboratory descriptionChecked 2026-10-11 · Supplier laboratory statement read; not adopted as a selected-unit performance result.
  4. Official heat-pump certificate imagesChecked 2026-10-11 · Both original CCC documents visually inspected; printed May 2025 expiry retained, not current status.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Langri exposed fan-coil terminals · Console and ceiling arrangements

Langri cassette fan coils · Panel layout and ceiling interfaces

Langri wall water-air-conditioning terminals · Piping and wall access