Use model mass, speed and mounting evidence; unconditioned circulation volume and a diagram ambiguity do not approve the room installation.
From Bigfans Wuhan · Large-space air-movement equipment
Individual product research · HVACDeck Editorial · Sources checked 2026-10-11
Bigfans’ Fengrui SFFCA family is described as a permanent-magnet synchronous-motor ceiling fan, with five diameters from 2.5 to 7.3 m. Its table supplies rotational speed, mass, motor power and voltage/current alternatives. SFFCA73 lists 7.3 m, 55 rpm, 127 kg and 1.5 kW; smaller SFFCA25 lists 2.5 m, 140 rpm, 35 kg and 0.4 kW. The nominal airflow row is in m³/min, without a stated measurement or installed pressure/room condition.
The original mounting diagram includes obstruction, travelling-crane and drop-rod notes. Its left text labels 2.5 m as building height, while the drawn dimension runs from ground to the blade plane; this needs a current issued installation drawing. Approve structural mounting and actual occupied-zone air delivery before choosing diameter. The series does not supply refrigeration capacity or proof of outdoor-air ventilation, even where circulation is marketed as cooling comfort.
This is an equipment family; its range does not identify one orderable configuration.
Swipe the table, or focus it and use arrow keys, to read the conditions and sources.
| Parameter | Published value | Conditions and evidence |
|---|---|---|
| Large model reference | SFFCA73: 7.3 m; 55 rpm; 127 kg; 1.5 kW motor | Motor power, not a measured installed energy-saving percentage. Source |
| Small model reference | SFFCA25: 2.5 m; 140 rpm; 35 kg; 0.4 kW | Nominal family choices; support and performance evidence required for the order. Source |
| Published airflow row | SFFCA73 15,850 m³/min; SFFCA25 6,500 m³/min | No measurement method or installed room/pressure basis; not outdoor-air exchange. Source |
| Voltage/current choices | SFFCA73: 3.5 A / 380 V or 5.5 A / 220 V | Source alternatives; phase, controller input and startup protections unprovided. Source |
| Original installation notes | Obstruction clearance ≥0.2 m; crane-to-beam ≥0.8 m; rod range 0–6 m | Supplier sketch only. Text/arrow scope for 2.5 m differs; obtain issued site-specific drawing. Source |
| Claim boundaries | PMSM, gear-free maintenance wording, 280 N·m and 35% airflow increase promoted | No exact torque-model basis, matched comparison, complete service procedure or independent report reviewed. Source |
Provide ceiling/support height, floor plan, workstations, racks and obstructions, together with the desired occupied-zone air-speed range. Obtain the selected diameter/speed layout and evidence for the actual room conditions. The table’s very large m³/min values cannot be used as outdoor-air supply or a duct-pressure selection.
Define comfort objectives separately from refrigeration and contaminant removal. No source temperature/humidity test establishes a fixed room-temperature reduction. Compare options through measured or agreed air distribution and input rather than an invented cooling tonnage.
The source sketch identifies obstruction clearance of at least 0.2 m and travelling-crane-to-beam spacing of at least 0.8 m, with a 0–6 m rod range. These notes do not settle the actual building loads, crane envelope or complete installed clearance. Supply a site drawing and obtain the selected mounting approval from the responsible parties.
The left label calls 2.5 m building height but the dimension arrow goes to the blade plane. Do not silently choose an interpretation or treat it as a universal approved minimum. Close blade plane, occupied routes, fixtures and service access with a current issued drawing.
Use the actual mass and rotational speed in support/drawing review; do not infer all dynamic loads from listed mass alone. Obtain hub/blade retention, supports and current installation instructions. The source image shows a suspended assembly and cable arrangement but provides no independently verified structural safety result.
Choose the 220 or 380 V configuration and obtain phase, wiring, controller demand, startup limits and protection requirements. Central/zone/temperature/humidity control is advertised, but no protocol or included sensor schedule is supplied. Confirm included options before integrating building controls.
The source calls the gear-free arrangement maintenance-free and claims long motor life. Obtain the actual inspection, fastening, cleaning and controller/bearing service requirements; absence of a gearbox does not establish that an overhead assembly needs no inspections. No independent ten-year-life result was reviewed.
Accept current drawings, model/BOM and applicable documentation, then verify direction/speed, electrical/control behaviour, occupied-zone delivery and agreed vibration/sound at actual operation. The 280 N·m and 35% improvement statements have no reviewed model/baseline scope. Price, delivery and installed energy savings remain unknown.
Model diameter, rpm, mass, motor power and voltage/current alternatives.
Issued support/clearance drawing and actual room-air delivery.
Input/test basis, control file, retention and service documentation.
Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.
Editorial method and corrections · Report a detail with this page URL
Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.