EQUIPMENT / EQUIPMENT FAMILY

Envicool CyberMate V inverter CRAC

A room-cooling family for changing computer-room loads; select the exact unit, air path and operating conditions before comparing capacity or efficiency.

From Shenzhen Envicool Technology Co., Ltd.

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

CyberMate V inverter computer-room air conditioning
Manufacturer catalogue image · CyberMate V
01 / UNDERSTAND THE EQUIPMENT

Turn a room-cooling proposal into a verifiable equipment selection

Envicool describes CyberMate V as an inverter computer-room air-conditioning family that responds dynamically to changing room loads and provides temperature and environment control. Its public page does not publish an exact model schedule or a numerical performance table. It is a starting point for an engineered selection, rather than a ready-to-order SKU.

There is also a naming detail to resolve: the page title says CyberMate V+ while its main body says CyberMate V. The quotation should identify the actual generation, complete model and document revision. This brief retains the body’s family name and does not assume that V and V+ have identical components or ratings.

The buying question is whether a selected configuration can serve the actual room layout and duty, including the load remaining when an agreed unit is unavailable. That answer needs a room-specific proposal and supporting performance data, not the broad capacity and energy-saving statements on linked solution pages.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
CyberMate V

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Published product identityCyberMate V inverter CRAC; browser title uses V+Family naming on the reviewed official page. The ordered generation and full model remain to be confirmed. Source
Published functionDynamic response to computer-room load changes; temperature and environment controlManufacturer description. No control tolerance, modulation limit or rated test point is specified in the readable product body. Source
Linked conventional-room solution6–300 kW across various productsSolution portfolio coverage, explicitly not a CyberMate V model-capacity schedule. Source

Selection and application review

Choose the cooling approach before choosing a model

The CyberMate page links several room and application solutions. Those links help frame a design discussion; they do not establish that one unit contains every feature or can substitute for all of the linked systems. Ask Envicool to identify which equipment and accessories belong in the proposed bill of supply.

Conventional room heat loads

The linked solution discusses air-supply arrangement, layouts and a broad portfolio. Return a room plan and load distribution, then request the proposed units, delivered duty and return/supply-air conditions. Do not select from the portfolio-wide 6–300 kW statement.

Read the source

Uneven or concentrated loads

A separate related card describes close-coupled cooling for uneven heat density. If the room has concentrated rack loads, ask whether a room CRAC arrangement is sufficient or whether the proposal needs separate equipment. The related card is not a CyberMate V performance guarantee.

Read the source

Dedicated humidity control

The linked humidity solution identifies HumidMate, wet-film humidification and ±5% RH at solution level. None of those numerical or construction details is established for the selected CyberMate V by this product page. Have the supplier identify included, optional and separate humidity equipment.

Read the source

Request a duty sheet that can be checked against the room

Send the room layout, rack/load map, current and planned sensible loads, target room conditions, available power and space constraints. Specify the intended duty and unavailable-unit scenario with the responsible designer. These are procurement inputs, not settings recommended by this platform.

Ask the supplier to return the full unit designation, cooling configuration, sensible and total capacity at the stated conditions, airflow and applicable external pressure, supply/return arrangement, unit and system electrical demand, and dimensions and service clearances. The public family page supplies none of those exact numerical values.

The response should identify connected components and options, any required outdoor equipment or water-side connections, and the boundaries of installation and commissioning. Do not assume a refrigerant, compressor type, fan arrangement or connection size from the word inverter.

Evaluate energy at the same system boundary

The conventional-room solution claims more than 30% air-conditioning-system energy savings and more than 10% data-center energy savings over a year. It provides no matched baseline, site weather/load profile or measurement dataset in the reviewed text. Those are supplier solution claims, not verified CyberMate V annual savings.

The product’s statement about reducing PUE is also qualitative. Request a comparison with the same load, operating hours, room targets and system boundary. Identify which electrical loads are included, the selected operating points and the assumptions used for part-load estimates. An individual unit’s rated power cannot establish an entire facility’s PUE.

Keep a separately documented projection and measured commissioning/operating results distinct. No energy-payback period, numerical efficiency or guaranteed saving has been added to this brief.

Make control and handover part of the enquiry

Dynamic load response is the stated product proposition, so the offer needs to explain how the selected configuration operates over the requested range. Use the following sequence to obtain a proposal that can be reviewed before order. It is editorial purchasing guidance, not a manufacturer commissioning procedure.

  1. Confirm identity and operating envelope

    Resolve V versus V+, name the full model/revision and request supported room/ambient conditions, capacity data, power and airflow. Ask for exclusions and the selection assumptions.

  2. Define operation and interfaces

    Request the actual control sequence, sensor scope, proposed communications, alarm behavior and any agreed unit rotation or standby function. Require the supplier to distinguish standard features from options or external controls.

  3. Agree delivery and acceptance

    List equipment, connections, installation, startup, training, spare parts and service responsibility. Agree how the room-specific duty and control response will be demonstrated, and obtain manuals and as-built settings for the supplied configuration.

Available evidence and the next useful document

The official download page returned no CyberMate match after a name search on 11 October 2026. Its visible default list instead showed liquid-cooling, energy-storage and ESG publications. This search result does not prove that a CyberMate manual is unavailable through sales or service.

The general selection page is an enquiry route, not a published CyberMate V sizing table. Request the current family brochure, exact model sheet, selected-duty performance data, installation/service manual and applicable compliance evidence directly for the proposed unit.

Envicool’s corporate profile and listed-company evidence help review the supplier. They do not validate this unit’s ratings, the displayed project reference or its performance at the buyer’s site. No price, delivery commitment, independently verified installation outcome or exact equipment certificate was established by the reviewed pages.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Envicool CyberMate V product pageChecked 2026-10-11 · Body and title naming difference retained; no exact numerical model table found in readable product text.
  2. Conventional heat-load data-center solutionChecked 2026-10-11 · Full solution text read; portfolio-wide capacity and unsubstantiated savings kept separate from product ratings.
  3. Data-center humidity-control solutionChecked 2026-10-11 · HumidMate and solution-level ±5% RH scope identified; not assigned to CyberMate V.
  4. Envicool documentation downloadChecked 2026-10-11 · CyberMate name search returned no listed document in this session; no claim of universal document absence.
  5. Envicool product selection and online supportChecked 2026-10-11 · Visible enquiry/selection route inspected; no exact CyberMate duty table established.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Continue the selection

Other equipment from this manufacturer

Envicool MC power-container cooling · Heating, humidity and dry contacts

Envicool BattCool-AC container cooling · Air paths and standby control

Envicool BattCool-C / EMW chillers · Battery coolant and fault duty

Envicool EMA cabinet air conditioners · Air path and filter service

Envicool HC combo cabinet cooling · Heat-pipe and compressor modes

Envicool DC / EC outdoor cabinet cooling · Power and selected duty