EQUIPMENT / EQUIPMENT FAMILY

Dunham-Bush WCFX-RH · Screw cooling and optional heat recovery

Define the actual water duty, oil-service scope and simultaneous recovery demand before comparing the high-efficiency family.

From Dunham-Bush (China) Industrial Co., Ltd.

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Dunham-Bush WCFX-RH · Screw cooling and optional heat recovery
Manufacturer catalogue image · WCFX-RH
01 / UNDERSTAND THE EQUIPMENT

Select cold-water output and recovered heat on matching conditions

WCFX-RH is a water-cooled fully hermetic screw chiller family with a published cooling range of 206–2293 kW. Dunham-Bush describes a vertical twin-screw compressor, built-in oil separation, falling-film evaporator, condenser subcooler and economizer. An electronic expansion valve is part of the stated design. This is a screw/oil-circuit selection, distinct from the separately reviewed oil-free centrifugal machines.

The source names HFC-134a and describes partial or full heat recovery as optional functions. Its all-series Chinese first-level efficiency and maintenance-free compressor wording lack an inspected selected rating/conformity report and complete service schedule. The webpage does not establish a heating output for either recovery option. A comparable enquiry should specify the simultaneous cold and recovered-heat duties and include tower, pump and control energy boundaries, rather than use the family cooling range as an ordered-model guarantee. RS485 is described as standard, while remote/group controls and protocol choices need order-specific confirmation.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
WCFX-RH

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Published cooling range206–2293 kWNo selected simultaneous-condition rating supplied. Source
Compression arrangementVertical fully hermetic twin-screw with internal oil separationMaintenance-free wording not a complete service exemption. Source
Heat-exchanger featuresFalling-film evaporator; condenser subcooler; economizerActual water pressure drops and operating map required. Source
Named refrigerantHFC-134aSelected charge and service documentation not reviewed. Source
Heat recoveryPartial or full recovery optionsNo source heating-capacity schedule; not assumed standard. Source
InterfacesStandard RS485; optional remote/group controls and protocol choicesActual registers and installed options required. Source

Selection and application review

Issue the cold and recovered-heat loads together

Provide chilled-water load/temperatures, condenser-water conditions and any simultaneous heat-demand profile. Ask for the selected model's cold duty, input and heat-recovery output at those exact conditions. Partial/full recovery options are not interchangeable with an independent heating-capacity guarantee.

Define where rejected heat goes when there is no useful heat demand and how the plant changes operating modes. Obtain the recovery exchanger arrangement and external pump/valve responsibilities. The official page does not supply the resulting temperatures or full-plant control sequence.

Approve screw and oil-service responsibilities

Obtain the selected compressor/oil circuit, oil type, separation/return requirements and protective alarms. The webpage describes a hermetic design and integrated oil separation; it does not prove that all leaks are impossible or that the complete chiller needs no inspections.

Require the actual maintenance and replacement-access schedule, including filters, valves, sensors and water-side cleaning where applicable. Confirm what can be serviced on site and what requires a compressor/module replacement. No service interval or lifetime warranty is invented.

Select hydraulics and efficiency with an issued rating

Request evaporator/condenser flow limits, pressure drops, water-quality requirements and the operating map for the falling-film/economizer arrangement. Compare complete machine input at matched conditions and include pump/tower effects in plant evaluation. The 206–2293 kW family span does not establish one selected unit's performance.

Ask for the applicable current model efficiency report and standard version behind the first-level efficiency claim. No issuer/conformity record was inspected here. Building LEED applicability is not product certification or independently measured project savings.

Commission ordered controls and recovery modes

Freeze RS485 wiring, the installed protocol, remote/group-control options and alarm responsibilities. Obtain registers, cause-and-effect diagrams and the changeover sequence for recovery demand, no-demand operation and relevant faults. General automatic monitoring language is not a selected interface contract.

Acceptance should verify selected cold/recovery duty, complete input, water flows, oil/protective states and the actual BMS integration. Obtain current price, delivery and spare/service terms directly; those commercial values remain unknown.

  1. Issue simultaneous duty

    Match cooling, condenser conditions and useful heat demand.

  2. Approve selected evidence

    Obtain rating, hydraulic limits, oil-service file and optional recovery scope.

  3. Witness mode changes

    Verify recovery/no-demand operation, protections and installed communications.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official WCFX-RH screw chiller pageChecked 2026-10-11 · Full range, screw/oil architecture and optional recovery/features read; original family rendering inspected.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Dunham-Bush ACTSXHP-R · Non-reversing defrost and radiator duty

Dunham-Bush WCOX · Industrial refrigeration skid and exchanger scope

Dunham-Bush LSCP · Open-screw compressor and oil-system package

Dunham-Bush AVX-R / ACX(HP)-HR · Outdoor screw duty and defrost

Dunham-Bush BWHP-E / WCSHP · Ground and water-source selection

Dunham-Bush integrated cooling station · Factory and site scope