EQUIPMENT / EQUIPMENT FAMILY

Dunham-Bush WCOX · Industrial refrigeration skid and exchanger scope

Select compressor and heat exchangers together, then define factory versus site testing for the actual skid arrangement.

From Dunham-Bush (China) Industrial Co., Ltd.

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Dunham-Bush WCOX · Industrial refrigeration skid and exchanger scope
Manufacturer catalogue image · WCOX
01 / UNDERSTAND THE EQUIPMENT

Freeze the industrial unit’s process, utility and shipping interfaces

WCOX is an industrial refrigeration unit family combining an LSC open screw compressor with shell-and-tube condensing and flooded-evaporator equipment. The source describes replaceable individual heat-exchanger tubes, a refrigerant-cooled oil cooler, slide-valve capacity control and optional vapour/liquid injection provisions. Small units are described as integrated assemblies, while larger orders use skids assembled on site. This package scope distinguishes WCOX from a compressor-only enquiry.

The headline −110 to 25°C range is a broad application statement without a selected staging, refrigerant or process-fluid schedule. The manufacturer lists several refrigerant choices and 10–99.99% capacity regulation, but neither provides a guaranteed complete operating map. A claimed factory performance test of at least 24 hours applies to the described small-unit delivery arrangement, not an independently witnessed test of every future order. Procurement should define selected heat exchangers, pressure vessels, shipping splits and on-site testing alongside compressor duty.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
WCOX

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Core arrangementLSC open screw with shell/tube condenser and flooded evaporatorSelected exchanger/vessel schedule required. Source
Published temperature span−110 to 25°CNot a selected single-stage or fluid rating. Source
Capacity-control statementSlide valve, 10–99.99%No inspected stability map across all conditions. Source
Delivery arrangementsIntegrated small units; site-assembled larger skidsActual shipping split and test scope need contract definition. Source
Service designIndividually replaceable exchanger tubes; field-serviceable bearingsActual access, isolation and repair procedures needed. Source
ControlsRS485 with open MODBUS describedSelected point list and interlocks not issued. Source

Selection and application review

Issue the process and refrigerant selections together

Specify process medium, heat duty, temperature/pressure limits and utility water conditions. Request the selected compressor map, refrigerant, stages and complete capacity/input rating. The broad temperature statement does not establish the achievable output of one quoted unit.

Obtain materials, corrosion/fouling limits, exchanger areas and pressure-vessel boundaries. Application lists do not establish suitability for any chemical medium or hazardous-area installation. Require project-specific documentation where these conditions apply.

Approve tube, oil and injection service access

Request exchanger drawings, removable bundle/tube access, cleaning/isolation procedure and allowable water-side pressure drops. Individually replaceable tubes are a source feature, not evidence that repair can occur without space or downtime.

Confirm refrigerant-cooled oil cooler requirements, mechanical seal service and the actual optional injection configuration. Obtain oil quality, return and protection documentation for the selected refrigerant and operating pressures. Do not assume both optional injection ports are fitted or active.

Separate factory tests from site assembly acceptance

Identify which unit is shipped complete and which skids require joining, alignment, charging or control wiring. Obtain weights, lifting/transport drawings and field assembly responsibilities. The small-unit description of at least 24 hours of testing does not confirm a witnessed order-specific result.

Agree factory test conditions, retained records and site repeat tests for pressure/leak integrity, controls and actual process duty. Determine commissioning utilities and responsibility for external piping or vessels.

Verify regulation and MODBUS in the real plant

Request the slide-valve operating map, minimum stable duty and startup/shutdown sequences. The 10–99.99% regulation claim is not a guarantee of equal efficiency or stability across arbitrary temperature lift.

Freeze RS485/MODBUS points, alarms, interlocks and supervisory authority. Acceptance should measure useful process duty, complete input and protective response at selected conditions. Price, delivery, exact-model conformity and independent installed performance remain unknown.

Thermal package

Select compressor, refrigerant, exchangers and pressure/material boundaries.

Shipping package

Define integrated/skid split, field assembly and repeat tests.

Operating package

Approve service access, regulation, interlocks and actual MODBUS scope.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official WCOX industrial unit pageChecked 2026-10-11 · Full compressor/exchanger/skid/testing and control descriptions read; original unit rendering inspected.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Dunham-Bush ACTSXHP-R · Non-reversing defrost and radiator duty

Dunham-Bush LSCP · Open-screw compressor and oil-system package

Dunham-Bush AVX-R / ACX(HP)-HR · Outdoor screw duty and defrost

Dunham-Bush BWHP-E / WCSHP · Ground and water-source selection

Dunham-Bush integrated cooling station · Factory and site scope

Dunham-Bush WCDSX-D · Low-temperature fluid and screw duty