AIRSYS CYBERCOOL-MOD DXA air-cooled room cooling

Fixed-speed scroll DX modules with EC air movement and condition-dependent outdoor condenser matching; pumped-refrigerant cooling is a separately specified option.

From AIRSYS precision and process cooling

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

AIRSYS CYBERCOOL-MOD DXA air-cooled room cooling
Manufacturer catalogue image · CYBERCOOL-MOD DXA
01 / UNDERSTAND THE EQUIPMENT

Match CYBERCOOL-MOD DXA indoor modules, condensers and remaining duty

CYBERCOOL-MOD DXA transfers equipment-room heat through a refrigerant circuit to an outdoor air-cooled condenser. The original C2104V03.5 catalogue identifies E1/E2 fixed-speed scroll compressor arrangements, modular cabinets and upflow/downflow supply. Its CW chilled-water version has different hydraulic interfaces and is not this DX selection.

The 40E2X1 column lists 43.6 kW total and 41.0 kW sensible at 24 °C/50% RH return and 35 °C outdoor. Raising return to 28 °C/50% RH at the same outdoor temperature gives 46.0/44.2 kW. Both figures belong to the same model with different rating conditions; neither is the cooling available after a compressor or common supply fails.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
CYBERCOOL-MOD DXA

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
40E2X1 at 24 °C return43.6 kW total / 41.0 kW sensible; return 50% RH, outdoor 35 °COriginal PDF page 16 DXA table, footnote 2. Source
40E2X1 at 28 °C return46.0 kW total / 44.2 kW sensible; return 50% RH, outdoor 35 °CSame column, footnote 3; different return condition. Source
Compressors / fanTwo fixed-speed scroll compressors; one EC backward-curved fan; 11,500 m³/h40E2X1 source schedule. Circuit independence and failure duty are not established by component count. Source
Electrical maximum380 V / 3Ph / 50 Hz; 18.9 kW maximum operating power, 34.6 A maximum operating currentTable entries, not rated energy use or a provided site protection selection. Source
40E2X1 condenser alternatives2 × CMEG8 at ≤43 °C ambient; 2 × CMEG10 for the ≥43 to ≤52 °C scheduleCatalogue matching footnotes; AMAE/VMEG alternatives are also listed. Exact current selected pairing must be approved. Source

Selection and application review

Size against sensible load and installed airflow

Send the equipment heat load, return temperature/humidity, required room or IT inlet limits and air-distribution arrangement. Select sensible capacity at those conditions rather than using the family maximum or a higher-return rating. Ask for delivered airflow at the installed resistance, filter condition and the chosen upper/lower supply arrangement.

The E1/E2 code describes compressor type/count. It does not promise that a two-compressor module is N+1, that both circuits are fully independent or that a failed circuit leaves the full load covered. Obtain the refrigerant, control and power dependency diagrams and the actual remaining sensible duty for agreed failure/maintenance states.

Order the correct condenser pairing for ambient and refrigerant runs

The same 40E2X1 indoor schedule changes its CMEG pairing with ambient conditions; AMAE and VMEG alternatives have their own source schedules. Obtain the selected indoor/outdoor model set, outdoor design ambient, capacity, fan power and full system input. A condenser's nominal label is not proof of the installed heat-rejection duty.

Close pipe lengths, vertical lift, sizes, refrigerant charge and installation instructions for the actual pair. Request the outdoor general arrangement, permitted unit spacing and service access. The V-shaped condenser option and compactness claims do not supply a site recirculation or noise assessment.

Treat RPU cooling as an ordered circuit and operating envelope

The catalogue describes a refrigerant-pump option that reduces compressor operation in cooler weather without admitting outside air. It adds a pump box and pipework, and the 40E2X1 column lists RPU22. Do not infer that a base DXA offer includes that assembly or that its pump can cover every load/ambient combination.

Require pump, hybrid and compressor-mode duties and transition temperatures, with controls and common dependencies. Ask for annual weather/load assumptions before accepting energy claims. The official webpage's average EER and fan-saving percentages are supplier statements, not measured performance of this selected installation.

  1. Approve the base DX pair

    Use the actual return, ambient and sensible-load condition.

  2. Approve the optional RPU circuit

    Define pump box, refrigerant paths, sensors and the useful low-ambient range.

  3. Witness transitions and failures

    Verify agreed mode changes and remaining duty without assuming component count establishes availability.

Set humidification, filtration and room interfaces explicitly

The DXA table lists G4 filtration, a default 6 kW heater and an 8 kg/h electrode humidifier for 40E2X1; another configuration may be quoted. Confirm included parts, selected output and current maintenance documents, with water supply quality, drains and electrical loads where applicable. The filter label alone does not establish a verified room cleanliness class.

The 40E2X1 source gives a 1,455 × 965 × 1,975 mm unit and 450 kg weight, with larger shipping dimensions. Obtain approved drawings for handling and final service space. Modular transport descriptions should be closed with the actual separation/reassembly instructions and site commissioning boundary.

Resolve the actual source version and acceptance requirements

The webpage's download label reads C2104V03.6, while the file inspected has C2104V03.5 on its cover. This brief uses the actual downloaded edition; obtain the current issued model schedule before ordering. Do not silently describe these fixed-speed E-series entries as the OPTIMA2 variable-speed compressor offer.

Obtain the selected controller, communications/licences, point list and network-loss behaviour. Define commissioning against selected sensible duty, airflow, humidity functions, alarms and remaining cooling states. Present certificates and warranty terms for the ordered supply market. The platform has not tested the equipment, certified an installation or verified stock/delivery.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official CYBERCOOL-MOD family pageChecked 2026-10-11 · Complete product description read; catalogue link label differs from actual cover version.
  2. Original CYBERCOOL-MOD catalogueChecked 2026-10-11 · Actual cover C2104V03.5. Model/cooling method pages 1–4 and DXA tables pages 16–17 reviewed; page 16 visually checked. Other tables not transferred into this DXA duty.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Continue the selection

Other equipment from this manufacturer

AIRSYS MOBILECOOL-OUTDOOR wall-mounted telecom cooling

AIRSYS DATACOOL-PACKAGE integrated room cooling

AIRSYS CYBERCOOL-MOD CW chilled-water room terminals

AIRSYS OPTIMA2 modular precision cooling

AIRSYS FREECOOL-HD high-density direct-air cooling

AIRSYS FREECOOL telecom ventilation retrofit