AIRSYS FREECOOL telecom ventilation retrofit
Manufacturer catalogue image · FREECOOL
01 / UNDERSTAND THE EQUIPMENT

Match FREECOOL's ventilation duty to the existing telecom room

FREECOOL supplements an existing telecom or small equipment-room air conditioner by admitting cooler outdoor air. It is a direct-air ventilation product, so outdoor-air suitability and an adequate exhaust route matter alongside temperature. The inspected C1801V02.1 catalogue describes indoor/outdoor and split/packaged arrangements with AC or DC supply; these choices do not all deliver the same measured airflow.

The model code's nominal airflow is not the performance table. For example, an 18F1 packaged unit lists 1,450 m³/h, whereas the split 18F1 lists 1,750 m³/h. Their listed cooling at a 10 °C indoor/outdoor difference is 4.9 and 5.9 kW respectively. This brief keeps those configuration differences visible rather than advertising one unconditional capacity or the supplier's 30–90% saving claim as a measured result.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
FREECOOL

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Cooling methodDirect introduction of cooler outdoor air; coordinated with existing air conditioningOfficial family description; useful operation depends on the room and outside-air conditions. Source
Packaged 18F1 example1,450 m³/h; 2.4 / 4.9 / 5.9 kW at Δt 5 / 10 / 12 °COriginal PDF page 6 performance table; not the split-unit value or a compressor rating. Source
Split 18F1 example1,750 m³/h; 2.9 / 5.9 / 7.1 kW at Δt 5 / 10 / 12 °CSame source table, different construction. Installed flow/external resistance still need selection. Source
Power variantsDC input 36–57 V; AC input 220 V ±15%Catalogue operating range. AC performance table specifically says indoor-installed units; do not infer every layout has either supply. Source
Environment limitsOperation −30 to +55 °C; storage −40 to +70 °CPublished component/working envelope, not an all-weather free-cooling capacity guarantee. Source

Selection and application review

Choose split or packaged construction using the room air path

A split unit has a main intake unit and separate air-discharge section. A packaged unit combines inlet/outlet and volume-control equipment. Identify wall openings, rain protection, discharge location and access on an actual room plan before selecting an indoor or outdoor installation. A supply fan without a coordinated discharge path cannot be accepted solely from a catalogue airflow.

The 18F1 examples illustrate why nominal codes should not decide the duty: the split version has higher listed airflow and cooling than the packaged version. Obtain the selected fan/room resistance point, dirty-filter allowance and the effect of the installed louvers and discharge assembly. Do not convert the 18 code directly into 1,800 m³/h delivered airflow.

Packaged arrangement

Integrated intake/discharge construction; 18F1 table airflow 1,450 m³/h and 4.9 kW at Δt 10 °C.

Split arrangement

Separate main and exhaust sections; 18F1 table airflow 1,750 m³/h and 5.9 kW at the same Δt.

Select capacity against weather and the room heat load

The table gives cooling at three temperature differences rather than one fixed refrigeration output. Establish the room set point, design heat load and acceptable temperatures when ventilation can only cover part of the load. Request the changeover and air-conditioner-assist sequence when outdoor air warms or fan capacity is insufficient.

Annual savings require hourly weather, load, permitted outside-air hours and the existing air conditioner's energy use. The website's 30–90% range does not supply those inputs and is not a verified saving for this room. Include ventilation fan energy and all operating modes in a project estimate.

Specify filter maintenance and humidity lockout as delivered equipment

The catalogue separates G4 washable filtration and G2 pre-filtration from optional items including a disposable filter, differential-pressure switch and humidity sensor. Require the actual filter specification, alarm equipment and replacement/cleaning instructions. Printed filter classes are source descriptions, not a reviewed present test report or proof that the room meets a required cleanliness standard.

Humidity control is listed as an option, not an inherent capability of every unit. Have the room designer specify when outdoor air must be blocked because of humidity, contaminants or other environmental conditions and how the existing cooling maintains the load in that state. Do not infer that a broad working humidity range makes every outdoor-air condition suitable for electronics.

Keep DC emergency ventilation distinct from refrigeration backup

The source explicitly limits continued operation from a base-station 48 V supply during mains failure to the DC product. An AC unit's controls or an optional 24-to-48 V converter entry do not establish a complete DC-backed installation. Confirm exact polarity/input limits, electrical protection, available supply capacity and the selected fan/control load.

Emergency ventilation can still be temperature-limited. Agree the allowed room temperature and the cooling/power failure sequence; it is not a guarantee that outdoor air will remove the full load during a hot-weather outage. Obtain a coordinated power and cooling design rather than treating the DC fan as a replacement for mechanical cooling.

Close retrofit controls and drawings before cutting openings

The family can coordinate one or two air conditioners; associated contactors and communications cards appear among optional equipment. Identify the existing equipment's control interfaces, the delivered contactors/points, alarm states and manual operating provisions. Request the exact current protocol map and permissions for any RS232, RS485 or PCOWEB interface.

The outdoor split 24F1 dimension table differs between the performance spread and the detailed drawing schedule. Use an approved model drawing to settle that discrepancy before wall work; no preferred dimension is assumed here. Obtain a dated quotation covering the complete assembly, current conformity documents, installation works and commissioned operating sequence. The platform has not tested FREECOOL or independently verified the webpage's ETL statement.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official FREECOOL retrofit pageChecked 2026-10-11 · Complete live description read; direct-air method, four installation forms and unverified savings/certification statements.
  2. Original FREECOOL catalogueChecked 2026-10-11 · Actual Chinese cover C1801V02.1. All eight PDF pages read; PDF page 6 technical spread visually inspected. Layout/power options and dimensional inconsistency preserved.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Continue the selection

Other equipment from this manufacturer

AIRSYS MOBILECOOL-OUTDOOR wall-mounted telecom cooling

AIRSYS DATACOOL-PACKAGE integrated room cooling

AIRSYS CYBERCOOL-MOD CW chilled-water room terminals

AIRSYS CYBERCOOL-MOD DXA air-cooled room cooling

AIRSYS OPTIMA2 modular precision cooling

AIRSYS FREECOOL-HD high-density direct-air cooling