Compare A/C arrangements at one defined air duty, keeping source medium limits and table defects attached to the enquiry.

From Gaobeidian Gerui · General and process-air fan manufacture

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Gerui 4-72 centrifugal fans · Duty, transmission and catalogue consistency
Manufacturer catalogue image · 4-72; A/C arrangement alternatives
01 / UNDERSTAND THE EQUIPMENT

Specify the airflow and drive as one selected assembly

Gerui's 4-72 centrifugal offer is presented on A- and C-arrangement pages. The reviewed C-family photograph shows a volute casing on a base with an external shaft/transmission enclosure, while the A picture is a compact motor-mounted assembly. They are consolidated into one 4-72 family because transmission and size alternatives should be selected together, rather than creating near-duplicate capacity or speed pages.

The official body permits ordinary air or other stated noncorrosive, nonflammable, nonsticky streams, with gas temperature no higher than 80°C and dust/hard-particle concentration no more than 150 mg/m³. Its schedules provide speed, paired flow/total-pressure ranges and motor columns. Some cells contain malformed motor text or multiple alternatives. A separate page headed 4-42 actually displays 4-72 tables; that mismatch is excluded as independent 4-42 evidence. This brief retains usable rows while requiring a current selected curve, drive arrangement and drawing.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
4-72; A/C arrangement alternatives

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Official medium boundaryNo corrosive, flammable, volatile or sticky gas; stated ordinary-air dutySupplier description, not an independently verified special-gas construction. Source
Published gas limits≤80°C; dust/hard particles ≤150 mg/m³Exact 4-72 description; not a dust-collector or abrasive-material guarantee. Source
C-family No.6C example1600 r/min; Y132S-4 5.5 kW; 7367–14734 m³/h; total pressure 1389–881 PaExact original row; selected point and air-reference/test basis still needed. Source
A-family No.6A example1450 r/min; Y112M-4 4 kW; 6677–13353; total pressure 1139–724 PaOriginal A table has malformed flow-unit typography; supplier must confirm units and selected point. Source
Arrangement evidenceC photograph: external transmission area; A photograph: compact motor-mounted assemblyFamily images read; precise drive, rotation and outlet position require issued drawings. Source
Catalogue defects retainedBlank A size cell, malformed C motor strings; 4-42 page contains 4-72 tablesNo guessed correction or separate 4-42 product claim. Source

Selection and application review

Select one point within the flow/pressure range

The No.6C 1600 r/min row lists 7367–14734 m³/h and 1389–881 Pa total pressure with a 5.5 kW Y132S-4. Those ranges do not mean the fan supplies maximum flow at maximum pressure simultaneously. Ask for the complete curve and a marked operating point against the actual system resistance.

Specify air conditions and whether the designer's requirement is static or total pressure. The source total-pressure table does not directly prove external static available at the installed duct terminals. Obtain a current selection and complete electrical-input basis; the motor kW column alone is not measured running consumption.

Compare A and C at equal duty and installed scope

The No.6A source row at 1450 r/min has a 4 kW Y112M-4 and different flow/pressure values from the C example. This is not an equal-duty efficiency comparison. Ask the supplier to select both proposed arrangements at the same defined flow, pressure and entering-air conditions.

Obtain the ordered transmission, motor speed, fan speed, drive guarding and service requirements. The family photographs show different external arrangements but do not establish a particular pulley ratio or maintenance interval. Include base/supports, vibration isolation, access and any starter or speed controller in the quotation comparison.

Keep contamination and temperature within the disclosed scope

The official description limits temperature to 80°C and dust/hard particles to 150 mg/m³, and excludes sticky and several hazardous/corrosive gas characteristics. Issue the actual contaminants and operating extremes. If the gas falls outside that scope, require a different documented selection rather than treating the general 4-72 family as a universal process-exhaust fan.

The dust limit is not an independently tested impeller-wear life or proof that a material-conveying system is suitable. Ask for the selected material, finish, inspection and cleaning provisions appropriate to the actual service. No special coating or certification is inferred from blue/red paint in the image.

Resolve source errors before approving dimensions or motors

The A table has a genuinely blank size entry among its rows. The C table includes malformed motor strings and cells listing two motor alternatives without a complete point mapping. The separately titled 4-42 page includes tables headed 4-72 B/C/D. Those errors are not silently fixed or used to extend this family into a new product claim.

Require a dated selected row, exact motor, rotation/outlet position, flange and foundation drawing, and the accepted test schedule. Agree balancing, mechanical run and duty verification for the ordered unit. Current price, delivery and witnessed efficiency remain unknown; the same family covers the actual transmission choices without multiplying nominal sizes into URLs.

  1. Set a comparable duty

    Provide paired flow/pressure, air conditions and source medium limits.

  2. Approve the drive and layout

    Name fan/motor speeds, transmission, guards, outlet/rotation and service space.

  3. Close catalogue conflicts

    Obtain corrected selection/drawings and ordered-unit acceptance records.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official 4-72 C arrangement and tableChecked 2026-10-11 · Full body, original family image and No.6C–10C HTML schedule reviewed.
  2. Official 4-72 A arrangement and tableChecked 2026-10-11 · Full body and original table/image reviewed; blank size and flow-unit typography retained.
  3. Official page headed 4-42Checked 2026-10-11 · Full page inspected: schedule headings are 4-72. Excluded as evidence for a separate 4-42 product.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Gerui G6-41 boiler air fans · Role and operating-point evidence

Gerui XQ air-slide process fans · Air duty and interface selection

Gerui 9-19 high-pressure centrifugal fans · Correct schedule and duty

Gerui GD30K2 axial fans · Motor arrangement and medium review

Gerui T35 axial fans · Operating point and total-pressure selection