MANUFACTURER / SOURCE REVIEW

Gaobeidian Gerui · General and process-air fan manufacture

Match a Hebei manufacturing identity and actual fan schedules while keeping old contact records, missing factory evidence and catalogue errors visible.

Gaobeidian, Hebei, China

Prepare a technical enquiry
6 published equipment referencesLatest source review 2026-10-11
01 / COMPANY

What this manufacturer offers

Gaobeidian Gerui Environmental Protection Fan Factory, legally 高碑店市格瑞环保风机厂, is a Hebei lead for general and process-air fans. The original CRM export records establishment on 18 March 2008 and credit code 91130684679900215Q. The official homepage independently states a 2008 start, and the current website contact locality agrees with the CRM registered address: within the Xishuo building-materials premises east of Guangwei Avenue, Fangguan, Gaobeidian. The CRM annual-report and correspondence fields retain an older Zhuanghuo locality; they have not been rewritten to make the records look uniform.

The reviewed catalogue contains actual T35 and GD30K2 axial schedules, 4-72 centrifugal arrangements and a 9-19 high-pressure schedule. It is useful for preliminary duty enquiries, but also contains malformed model strings, blank size cells and tables filed under the wrong headings. Gerui describes fabrication, tooling and balancing capability; its present equipment and honour sections display no items. This profile therefore evaluates the disclosed products and source consistency without claiming a factory visit, an independently audited production rate or current certification.

CRM dated legal record
18 March 2008; 高碑店市格瑞环保风机厂Preserved original export; official homepage independently states 2008, not a fresh live registry audit. Source
Matched registered/official contact locality
Xishuo premises, east of Guangwei Avenue, Fangguan, GaobeidianCurrent website matches CRM registered address; older annual/correspondence addresses retained. Source
Actual reviewed portfolio
T35; GD30K2; 4-72 A/C; 9-19 high-pressure; XQ process-airIndividual official product bodies/schedules read; not every site heading matches the included tables. Source
Reported fabrication and inspection
Machining, balancing equipment and dedicated forming toolsSupplier statement; current equipment gallery has no items and no calibration/throughput audit. Source
Industry-platform cross-check
Same exact factory name and two matching mobile numbers on China Fan NetworkSupplier-style listing with older Xinglong Avenue address, not independent factory certification. Source
Current honour/gallery disclosure
No items shown in reviewed honour or equipment sectionsAn empty website section is not proof that the enterprise has no equipment or credentials. Source
Important catalogue mismatch
4-42 heading displays 4-72 tables; high-pressure page includes Y8-39/Y9-38 schedulesThose mismatched blocks are not used to create new product claims or padded URLs. Source
02 / EQUIPMENT

Published equipment and selection evidence

Parameters and source limits · G6-41; source body GY6-41

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · G6-41; source body GY6-41
ParameterPublished valueConditions and evidence
Source title/body distinctionTitle G6-41; body GY6-41Exact supplier terminology; ordered supply/induced-draft role must be stated. Source
Published boiler context0.5–10 t/h industrial boilers with smoke/dust removalSupplier application range, not fan flow, a boiler retrofit approval or whole-system capacity guarantee. Source
No.5.4A example1420 r/min; Y100L2-4B3 3 kW; flow 4358–2130 m³/h; total pressure 994–1254 PaExact printed endpoint order; complete selected curve and gas-reference condition absent. Source
No.6.4A example1440 r/min; Y132S-4B3 5.5 kW; flow 7358–3596 m³/h; total pressure 1436–1811 PaDifferent schedule size, not an equal-duty electrical comparison. Source
Efficiency statementSupplier claims peak total-pressure efficiency above 80%No reviewed method, test point or selected-unit witnessed result. Source
Unstated selected duty boundariesGas temperature/composition, pressure convention, materials and complete inputDo not borrow hot-gas limits from unrelated Y5-47 or other catalogue pages. Source
Parameters and source limits · XQ 4.7A / 4.8A / 5.4A

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · XQ 4.7A / 4.8A / 5.4A
ParameterPublished valueConditions and evidence
Published positioningCement-kiln air-slide fan; other forced-air furnace uses mentionedSupplier application, not verified whole-process design or installed reference. Source
Actual schedule sizes4.7A, 4.8A and 5.4A at 2840 r/minSingle genuine family; size/motor rows consolidated. Source
4.7A row exampleY90S-2 1.5 kW; 585 m³/h; total pressure 5187 PaExact supplier row; reference air condition and measured electrical input absent. Source
5.4A row exampleY100L-2 3 kW; 727.5–860 m³/h; total pressure 6918–6858 PaSame 2840 r/min schedule; selected curve required rather than an arbitrary maximum pair. Source
Temperature and particles≤80°C; dust/hard particles ≤150 mg/m³Source limits with noncorrosive/nonflammable/nonsticky exclusions. Source
Unestablished package scopeAir-slide internals, distribution, motor controls and complete installationNo whole-line design, flow uniformity or material-through-rotor approval inferred. Source
Gerui 9-19 high-pressure centrifugal fans · Correct schedule and duty
series REFERENCE

Gerui 9-19 high-pressure centrifugal fans · Correct schedule and duty

Catalogue reference: 9-19 No.4A–16D; 9-26 ratings unverified

Open the equipment selection brief
Parameters and source limits · 9-19 No.4A–16D; 9-26 ratings unverified

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · 9-19 No.4A–16D; 9-26 ratings unverified
ParameterPublished valueConditions and evidence
Actual table identity9-19 No.4A–16DSame block repeated on A/D pages; no corresponding 9-26 schedule verified. Source
No.4.5A example2900 r/min; Y112M-2 4 kW; 1174–2062 m³/h; total pressure 4603–4447 PaExact original 9-19 row; reference air condition and measured input/efficiency absent. Source
No.10D example1450 r/min; Y200L-4 30 kW; 6440–12450 m³/h; total pressure 5840–5495 PaDifferent size/drive row, not an equal-duty efficiency comparison. Source
Published temperature/contaminationGenerally ≤50°C; maximum 80°C; dust/hard particles ≤150 mg/m³Supplier family wording; actual medium and operating envelope require confirmation. Source
Original pictured arrangementVolute, top rectangular outlet and rear motor on supportImage observed; outlet angle, rotation, pressure rating and guarding not issued. Source
Unrelated appended schedulesY8-39 and Y9-38 blocks excludedNo blanket range spanning different fan families, and no 9-26 values inferred. Source
Parameters and source limits · 4-72; A/C arrangement alternatives

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · 4-72; A/C arrangement alternatives
ParameterPublished valueConditions and evidence
Official medium boundaryNo corrosive, flammable, volatile or sticky gas; stated ordinary-air dutySupplier description, not an independently verified special-gas construction. Source
Published gas limits≤80°C; dust/hard particles ≤150 mg/m³Exact 4-72 description; not a dust-collector or abrasive-material guarantee. Source
C-family No.6C example1600 r/min; Y132S-4 5.5 kW; 7367–14734 m³/h; total pressure 1389–881 PaExact original row; selected point and air-reference/test basis still needed. Source
A-family No.6A example1450 r/min; Y112M-4 4 kW; 6677–13353; total pressure 1139–724 PaOriginal A table has malformed flow-unit typography; supplier must confirm units and selected point. Source
Arrangement evidenceC photograph: external transmission area; A photograph: compact motor-mounted assemblyFamily images read; precise drive, rotation and outlet position require issued drawings. Source
Catalogue defects retainedBlank A size cell, malformed C motor strings; 4-42 page contains 4-72 tablesNo guessed correction or separate 4-42 product claim. Source
Gerui GD30K2 axial fans · Motor arrangement and medium review
series REFERENCE

Gerui GD30K2 axial fans · Motor arrangement and medium review

Catalogue reference: GD30K2; four/six-blade alternatives

Open the equipment selection brief
Parameters and source limits · GD30K2; four/six-blade alternatives

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · GD30K2; four/six-blade alternatives
ParameterPublished valueConditions and evidence
Supplier applicationHumid or motor-adverse gas streams; duct intermediate installationBroad application description, not universal chemical/hazardous-gas compatibility. Source
Published temperature boundaryGas temperature must not exceed 60°CExact body limit; no special high-temperature or smoke-exhaust option verified. Source
Original pictured constructionAxial casing with motor above it and external transmission areaPhoto inspected; seal details, exact transmission and ordered materials require issued drawings. Source
Four-blade No.10 example960 r/min; Y132M1-6 4 kW; 22600–29700 m³/h; total pressure 206 PaClearly identified original table row; reference air/gas and complete curve absent. Source
Six-blade No.10 example960 r/min; Y132M1-6 4 kW; 24000–30000 m³/h; total pressure 226–255 PaSeparate blade-count schedule; not a guaranteed adjustable conversion of the same delivered unit. Source
Source defectsSeveral actual size cells blank; motor typography inconsistentOriginal table HTML checked; unidentified rows not assigned guessed sizes. Source
Gerui T35 axial fans · Operating point and total-pressure selection
series REFERENCE

Gerui T35 axial fans · Operating point and total-pressure selection

Catalogue reference: T35; size and speed alternatives consolidated

Open the equipment selection brief
Parameters and source limits · T35; size and speed alternatives consolidated

Swipe the table, or focus it and use arrow keys, to read conditions and sources.

Manufacturer-published information · T35; size and speed alternatives consolidated
ParameterPublished valueConditions and evidence
Published applicationGeneral factory, warehouse, office and residential ventilationSupplier scope; not a smoke-exhaust, explosive-gas or corrosion approval. Source
Original family constructionAxial rotor, cylindrical flanged casing and support baseSupplier family photograph inspected; selected guards, dimensions and drive remain to be issued. Source
Actual No.5.6C example1450 r/min; YSF-7124 motor 0.37 kW; 6025 m³/h; total pressure 140.9 PaExact row in the second official table; reference air condition and independent test basis absent. Source
No.5.6C higher motor row1450 r/min; YT90S-4 1.1 kW; 11110–12239 m³/h; total pressure 182.1–206 PaPublished operating-range row, not an arbitrary combined maximum point. Source
Motor-power meaningListed 配用电机 kW is the selected motor columnNot established as measured fan/package electrical input. Source
Remaining selection evidenceCurve, air-reference conditions, static/total convention, sound and dimensionsNo inferred pressure reserve, efficiency or room-area performance. Source
03 / PROJECT REVIEW

Evaluate the fan and the disclosure behind its selection

Establish the contract and location without erasing history

The legal name is a factory-form business name, rather than a differently named limited company. Use the exact current contracting identity and request its current registration/quotation details. The preserved CRM date and current homepage's 2008 statement agree at year level. The credit code comes from the original export; no newly downloaded government licence was inspected.

The current official contact address agrees with the CRM registered address. Older CRM annual/correspondence fields and the industry-platform listing use other localities. Treat them as dated source differences and ask where the selected fan is currently fabricated and dispatched. Do not portray every address as a simultaneously operating branch.

Review the manufacturing claim against the ordered fan

The company description claims machining, balancing equipment, forming tools and nonstandard fabrication. The presently reviewed production-equipment page says no content is displayed. The company-page graphic is a promotional mountain image, not a photograph of a factory. No invented machine inventory, floor area or production capacity is added.

Request a current process map and evidence for the ordered impeller, casing and drive: material traceability, forming/welding, dimensional checks, balance record, final rotation/run checks and the agreed fan-performance test. If any parts are purchased, ask who supplies and verifies them. General quality language is not an issued acceptance report.

Choose the correct general or process-air offer

T35 is presented for ordinary building/factory ventilation. GD30K2 addresses a different motor/gas arrangement for humid or motor-adverse streams, with a stated 60°C limit; it is not automatically certified for every hazardous gas. The 4-72 body limits temperature and contamination and excludes corrosive, flammable and sticky streams. The high-pressure and XQ process-air descriptions require their own medium and duty review.

Issue the actual gas, temperature, composition, contamination, required volume flow and pressure convention. Match an operating point and selected drive to the system. Do not equate maximum table flow with maximum table pressure at the same point, or a motor kW column with measured complete equipment input.

Keep catalogue inconsistencies in the enquiry

The 4-72 A page includes a blank size cell, while the C schedule contains malformed motor strings and several multiple-motor entries. The page headed 4-42 has tables explicitly labelled 4-72. The 9-19/9-26 page includes separate Y8-39 and Y9-38 tables after its actual 9-19 schedule. These blocks are not merged into one fabricated range or silently corrected.

Ask for a current model-specific curve, selected row, motor, rotational speed and issued dimensional drawing. The product briefs identify usable examples and the remaining conditions rather than republishing every defective cell. Sizes, speeds, transmission choices and duplicated entries are consolidated within genuine families.

Use the platform listing for identity, not endorsement

China Fan Network's company page repeats the exact factory name and both mobile numbers found on the official site, while giving an older Xinglong Avenue address. It describes the same broad fan manufacture and a complete-unit trial-run claim. This is useful supplementary listing evidence, not a witnessed audit or proof of a current compliance certificate.

The official contact page has separate office, sales and service email strings; the malformed technical-email string contains a space. Only the valid official sales address is selected for the private CRM field, without guessing a repair or using inconsistent older platform emails. No outreach has been sent. Current price, delivery, measured efficiency and independently verified installation outcomes remain unknown.

Identity agreement

Exact name and matching official mobile numbers support the listing cross-check.

Read the source

Historical differences

Older address and platform email strings are retained as source differences, not current branches.

Read the source

Evidence still needed

Obtain current selected-model production, test and conformity documents before contract acceptance.

Read the source
07 / TRANSPARENCY

Sources and review scope

Compiled by HVACDeck Editorial. Page review: 2026-10-11. Publications are attributed below; their statements are not independent measurements by this platform.

  1. Official Gerui company page and homepageChecked 2026-10-11 · Complete company description and original branding read; homepage 2008 statement checked, generic graphic not treated as factory evidence.
  2. Official contact pageChecked 2026-10-11 · Full locality and departmental emails read; malformed technical-email string not corrected.
  3. Official equipment and honour sectionsChecked 2026-10-11 · Equipment and honour sections both inspected; no items shown, with no inference about actual equipment ownership.
  4. China Fan Network company listingChecked 2026-10-11 · Full exact-company page read; matching name/phones, older address and discrepant email strings noted as listing evidence.
  5. Official T35 scheduleChecked 2026-10-11 · Complete body and two actual model tables read; selected examples retain speed, motor and total-pressure scope.
  6. Official G6-41 boiler fan detail and scheduleChecked 2026-10-11 · Full body, directly associated eight-size HTML schedule and original family image reviewed; G/GY wording and endpoint order retained.
  7. Official XQ air-slide fan pageChecked 2026-10-11 · Entire body and actual three-size HTML schedule read; application and medium limits retained with model-specific examples.
  8. Official A-titled high-pressure pageChecked 2026-10-11 · Full body, original image and all four table blocks read; only correctly named 9-19 examples adopted.
  9. Official D-titled high-pressure pageChecked 2026-10-11 · Full body and repeated/mixed schedules read; consolidated without duplicating a product URL.
  10. Official 4-72 C arrangement and tableChecked 2026-10-11 · Full body, original family image and No.6C–10C HTML schedule reviewed.
  11. Official 4-72 A arrangement and tableChecked 2026-10-11 · Full body and original table/image reviewed; blank size and flow-unit typography retained.
  12. Official page headed 4-42Checked 2026-10-11 · Full page inspected: schedule headings are 4-72. Excluded as evidence for a separate 4-42 product.
  13. Official Gerui GD30K2 description, table and imageChecked 2026-10-11 · Complete body and original table HTML read; blank size cells confirmed. Original motor/casing photograph visually inspected.

How we review sources · Represent this factory or request a correction