Gerui G6-41 boiler air fans · Role and operating-point evidence

Clarify supply versus induced-draft duty and the actual gas conditions before selecting the correctly associated schedule.

From Gaobeidian Gerui · General and process-air fan manufacture

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Gerui G6-41 boiler air fans · Role and operating-point evidence
Manufacturer catalogue image · G6-41; source body GY6-41
01 / UNDERSTAND THE EQUIPMENT

Match the boiler interface to a named fan duty

Gerui titles this offer G6-41 boiler centrifugal ventilation, while its body uses the combined GY6-41 designation for boiler supply/induced-draft applications. The stated context is industrial coal-fired boilers of 0.5–10 t/h with smoke/dust-removal equipment. That boiler-size description is not a fan airflow rating or proof that one unit can supply both air and hot flue-gas service. The exact role, gas conditions and current model must be clarified with the supplier and responsible boiler-system designer.

Unlike several misplaced boiler tables elsewhere in the site, this page presents an eight-size schedule directly beneath its G6-41 offer. It lists rotational speed, motor, flow and total pressure, including flow ranges printed in descending order. This brief preserves those source endpoints and the G/GY naming boundary. It neither converts the supplier's claimed above-80% peak total-pressure efficiency into a witnessed result nor supplies combustion settings or an operating procedure.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
G6-41; source body GY6-41

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Source title/body distinctionTitle G6-41; body GY6-41Exact supplier terminology; ordered supply/induced-draft role must be stated. Source
Published boiler context0.5–10 t/h industrial boilers with smoke/dust removalSupplier application range, not fan flow, a boiler retrofit approval or whole-system capacity guarantee. Source
No.5.4A example1420 r/min; Y100L2-4B3 3 kW; flow 4358–2130 m³/h; total pressure 994–1254 PaExact printed endpoint order; complete selected curve and gas-reference condition absent. Source
No.6.4A example1440 r/min; Y132S-4B3 5.5 kW; flow 7358–3596 m³/h; total pressure 1436–1811 PaDifferent schedule size, not an equal-duty electrical comparison. Source
Efficiency statementSupplier claims peak total-pressure efficiency above 80%No reviewed method, test point or selected-unit witnessed result. Source
Unstated selected duty boundariesGas temperature/composition, pressure convention, materials and complete inputDo not borrow hot-gas limits from unrelated Y5-47 or other catalogue pages. Source

Selection and application review

Close the air or flue-gas role with the boiler designer

The title says G6-41 ventilation while the body discusses GY6-41 supply/induced draft together. Ask the supplier to identify the exact selected model and gas path. Give the actual gas composition, temperature, contaminants, required volume flow and pressure at the fan boundary.

A boiler's tonnes-per-hour designation does not establish the required fan point. Its air/flue-gas system and smoke/dust-removal equipment need the responsible designer's actual specification. Do not assume the pictured fan is approved for hot flue gas, nor substitute an unrelated catalogue temperature limit. This brief is a sourcing review, not a combustion or retrofit instruction.

Read the descending flow endpoints without correcting them

For No.5.4A the source prints 4358–2130 m³/h and 994–1254 Pa with a 3 kW motor at 1420 r/min. The larger No.6.4A row has a different speed, motor and flow/pressure interval. The endpoint direction has been preserved; it is not silently sorted into a clean-looking new rating.

Obtain a current curve with the required point marked, reference gas conditions and the same static/total pressure convention used by the system designer. The table's motor column does not prove actual complete electrical input, and range endpoints do not describe arbitrary paired maxima.

Put the claimed efficiency on a checkable basis

The body claims peak total-pressure efficiency over 80%. It gives no reviewed method or operating point demonstrating that value for the ordered configuration. Ask for the applicable original test report and the efficiency/input calculation at the actual selected duty.

Include motor/drive/control and quoted accessories in the electrical comparison. Request noise and vibration data at the named speed and test boundary. No percentage saving, silent operation or universal high-efficiency badge is inferred from the general description.

Approve the mechanical and controls interfaces

Require the ordered material, rotor/casing arrangement, rotation/outlet position, support/connection drawing and manufacturer maintenance instructions. Agree which starter/control and protection items are supplied and how fan status/fault information interfaces with the responsible boiler control design. The product page does not establish a certified interlock or an installed safety function.

Define balance/run and performance acceptance for the exact selected fan, with gas/air measurement boundaries stated. Any boiler-system commissioning or emissions acceptance has its own responsible scope. Current price, delivery and independent installed outcomes are unknown; this one page consolidates the actual eight-size schedule without creating boiler-size or motor-power URLs.

  1. Define the role

    Get the responsible designer’s air/flue-gas duty and actual medium conditions.

  2. Select the real point

    Request a named model, curve, motor and current mechanical/electrical dossier.

  3. Separate acceptance scopes

    Agree fan-duty checks without representing them as boiler, emissions or safety-system approval.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official G6-41 boiler fan detail and scheduleChecked 2026-10-11 · Full body, directly associated eight-size HTML schedule and original family image reviewed; G/GY wording and endpoint order retained.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Gerui XQ air-slide process fans · Air duty and interface selection

Gerui 9-19 high-pressure centrifugal fans · Correct schedule and duty

Gerui 4-72 centrifugal fans · Duty, transmission and catalogue consistency

Gerui GD30K2 axial fans · Motor arrangement and medium review

Gerui T35 axial fans · Operating point and total-pressure selection