EQUIPMENT / EQUIPMENT FAMILY

HBO hot-air ducts · Insulation, flexibility and connected limits

Compare two disclosed constructions within one family, preserving their own pressure, temperature and dimension statements.

From Hunan HBO · Industrial electric hot-air manufacture

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

HBO hot-air ducts · Insulation, flexibility and connected limits
Manufacturer catalogue image · Hot-air duct family; insulated/flexible construction and dimensions consolidated
01 / UNDERSTAND THE EQUIPMENT

Choose the duct construction for the actual connected hot-air duty

HBO's hot-air duct offer includes an insulated silicone/glass-fibre construction and a metal-clipped flexible construction. The official insulated-page text and poster give diameters 25–600 mm, a stated 28 mm tube thickness, −70 to +300°C and 3,000 Pa rated pressure resistance. The 450°C flexible-page text and poster instead give diameters 51–1,500 mm, 0.50 mm thickness, −70 to +450°C and 10,000 Pa resistance. They are kept as construction choices on one duct-selection page, rather than separate URLs for every diameter or temperature label.

The decision is not simply which hose has the largest temperature number. The insulated option describes silicone/glass-fibre duct with external glass-fibre insulation; the flexible option describes coated glass-fibre fabric and a metal clamp construction with a stated compression ratio. The source supplies no inspected pressure-versus-temperature derating, vacuum-collapse limit, bend-loss schedule or current fire-test report. A quoted hot-air system therefore needs the actual selected duct and its connection ratings checked together.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
Hot-air duct family; insulated/flexible construction and dimensions consolidated

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Insulated constructionSilicone/glass-fibre duct with glass-fibre insulationOfficial description and actual stacked-duct image inspected; insulation performance not independently measured. Source
Insulated stated envelopeØ25–600 mm; thickness 28 mm; −70 to +300°C; 3,000 PaSupplier text/poster; thickness definition and pressure/temperature pairing need confirmation. Source
Flexible stated envelopeØ51–1,500 mm; thickness 0.50 mm; −70 to +450°C; 10,000 PaDistinct coated-fabric/metal-clipped construction; not a combined rating for the insulated offer. Source
Flexible geometry claimsBend radius approximately outside diameter; compression 1:10Supplier statement without inspected cycling or bend-loss test. Source
Missing system limitsTemperature derating, suction/collapse, connection rating and flow lossNo assumed vacuum capability, tested fire class or touch-safe outer surface. Source

Selection and application review

Select a construction before choosing a diameter

The insulated offer has a silicone/glass-fibre inner route and added insulation. The flexible offer describes a coated glass-fibre fabric, reinforced fibre and metal-clipped construction. Keep those materials and stated thicknesses attached to their own choice; do not describe a single hose as having both sets of ratings.

Ask whether the 28 mm insulated thickness is an overall construction thickness and obtain an issued section drawing. Specify the actual inlet/outlet size and connection arrangement. Diameter variants stay on one page because they do not create distinct process capabilities by themselves.

Check temperature and pressure simultaneously

The supplier prints a temperature range and a pressure-resistance value for each construction, but provides no inspected combined derating curve. Issue the actual continuous and transient air temperature, pressure differential and air composition. Obtain the selected manufacturer's allowable duty with the actual end connections, not just the largest separate catalogue values.

Do not connect a 350°C-labelled heater at that upper envelope to the insulated option's stated +300°C limit without a documented selected system design. Ask separately about suction/collapse if the route is an extraction line; a positive pressure-resistance number is not proof of vacuum performance.

Resolve flow loss, bends and mechanical service life

Specify the route length, bend geometry and required delivered flow. Ask for pressure-loss information at the ordered diameter and extension state, plus support and permissible movement instructions. The flexible page's approximate bend-radius and 1:10 compression statements do not establish zero flow loss or unlimited flexing life.

Obtain abrasion/contamination compatibility and replaceable connection details for the actual stream. Broad descriptions mentioning smoke, dust or exhaust are not a tested approval for every chemical or combustible contaminant. No fire classification is asserted without a traceable report for the selected construction.

Compare insulation and installed acceptance

The insulated illustration presents reduced heat release, but no independently measured thermal conductivity, surface temperature or system energy-saving percentage was reviewed. Define any external-surface requirement and ask for evidence under the selected duty. Insulation does not automatically make all hot connections touch-safe.

Acceptance should verify the ordered materials/dimensions, connection integrity, delivered flow and permissible thermal/pressure duty using issued supplier instructions. Current price, lead time and tested service lifetime remain unknown. Different diameters, lengths and temperature constructions remain selections within this consolidated offer.

Insulated silicone/glass-fibre route

Disclosed +300°C and 3,000 Pa statements with external insulation; confirm the actual thickness and outer-surface requirement.

Read the source

Flexible metal-clipped route

Disclosed +450°C and 10,000 Pa statements with 0.50 mm fabric construction; confirm bends, extension and combined duty.

Read the source

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official HBO insulated hot-air ductChecked 2026-10-11 · Complete technical text and original construction/parameter poster inspected; no inferred insulation test or derating.
  2. Official HBO 450°C flexible ductChecked 2026-10-11 · Complete technical text and original poster inspected; construction limits remain separate, diameters not padded into URLs.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

HBO wall-mounted fan heaters · Air distribution and mounting scope

HBO industrial heat guns · Air source and localized thermal duty

HBO temperature-control boxes · Sensor, load and protection scope

HBO air knives · Slot geometry, source pressure and drying acceptance

HBO circulating hot-air packages · Return-air temperature review

HBO portable 3–10 kW hot-air heaters · Supply and process selection