EQUIPMENT / EQUIPMENT FAMILY

Envicool in-row plate-exchanger CDU · Two-loop and control scope

Select the exchanger duty, variable-flow limits and available pump/filter options with actual server and facility-fluid requirements.

From Shenzhen Envicool Technology Co., Ltd.

Individual product research · HVACDeck Editorial · Sources checked 2026-10-11

Envicool in-row plate-exchanger CDU · Two-loop and control scope
Manufacturer catalogue image · In-row plate-exchanger CDU
01 / UNDERSTAND THE EQUIPMENT

Define the two liquid circuits before ordering the in-row CDU

Envicool's in-row CDU uses a plate heat exchanger to transfer heat from a circulating load-side liquid loop. The official page identifies a cabinet, water pump, plate exchanger, valves, expansion tank and piping, with stainless-steel pipeline construction and dual power supplies. It lists available single- or double-pump variable-frequency systems, an available 50 μm filtration device, adjustable flow of 10–100% and 7-inch/10-inch displays. The original cabinet rendering provides appearance without an ordered capacity or circuit rating.

The distinguishing procurement task is to define the two exchanger circuits and server-fluid requirements alongside the selected control and protection package. This page does not turn the supplier's 50 μm 'ultra filtration' wording into a microbiological purification grade, or treat available pump/filter choices as standard inclusions. Anti-condensation, water-quality monitoring and online maintenance are source-described features that require the actual settings, sensors and isolation arrangement. No heat-transfer capacity or pump head was published in the reviewed feature text.

02 / READ THE CONDITIONS

Published parameters and their scope

This is an equipment family; its range does not identify one orderable configuration.

Family designation
In-row plate-exchanger CDU

Swipe the table, or focus it and use arrow keys, to read the conditions and sources.

Manufacturer-published values · conditions are part of the specification
ParameterPublished valueConditions and evidence
Disclosed constructionPlate exchanger, pump, valves, expansion tank and pipingSelected capacity/material grade and arrangement not issued. Source
Pipeline and power featuresStainless-steel pipeline; dual power suppliesNo grade, design pressure or independence schedule inspected. Source
Available pump systemsSingle/double pumps with variable-frequency driversOptions; not every quote includes dual pumps. Source
Published flow modulation10–100%No absolute flow, head or selected stable operating range supplied. Source
Available filtration50 μm deviceSupplier calls it ultra filtration; no microbiological/membrane qualification inferred. Source
Monitoring/protection listWater quality, leak detection, overpressure, anti-condensation and group controlOrdered sensor list, thresholds and control sequence required. Source
Display options7-inch/10-inch colour displayConfiguration choices, not proof of calibrated thermal metering. Source

Selection and application review

Issue both sides of the plate exchanger

Provide facility-side fluid, temperatures, available flow/pressure and water quality separately from the server-side coolant specification and load. Ask for the selected exchanger approach, duty and pressure drops at those simultaneous points, plus material compatibility and design pressure. The page gives no heat-transfer capacity schedule.

Obtain the P&ID identifying pumps, valves, expansion volume, sensors and isolation on each circuit. Assign responsibility for upstream heat rejection and downstream manifolds/cold plates. A list of components does not establish which fluid circuit every listed part occupies.

Select pumps using absolute flow and pressure needs

Request the actual pump configuration and curves against the complete load-side resistance and permitted server pressure. The stated 10–100% modulation is a relative adjustment range; it does not provide litres per minute, pump head or stable duty at the lowest setting.

Clarify whether a single or double pump system is quoted, how variable-frequency control responds to load changes and what duty remains after a pump fault. Agree minimum-flow protection and server response. Dual power alone does not establish complete hydraulic redundancy.

Specify fluid quality and the 50 μm option precisely

Select fluid chemistry and wetted materials against the server OEM's requirements. Ask which water-quality properties are measured, their sensors/ranges and their alarm limits. Online water-quality monitoring is not proof that every contamination or chemistry change is detected.

If the 50 μm filter is ordered, request its element, removal basis, pressure-drop/maintenance limits and compatibility. Retain the published size without converting the marketing 'ultra filtration' phrase into a sterile-fluid or membrane-performance claim. Agree clean filling, flushing and sampling records.

Close condensation, pressure and replenishment controls

Request the actual coolant temperature control and dew-point measurement strategy behind anti-condensation. Define pressure limits, protection devices and automatic replenishment source/quality. No universal condensation-free or pressure-safe operation is inferred from a feature list.

Obtain alarm cause-and-effect and interfaces for leakage, overpressure, low flow and high temperature. Clarify group control and power-loss/restart behaviour. The available display sizes do not define the installed sensors or make displayed values independently witnessed measurements.

Agree online service and selected acceptance

Ask which components can be isolated and serviced while the server load continues, what temporary derating applies and how contamination is prevented during intervention. Obtain issued maintenance procedures and spare/consumable responsibilities.

Acceptance should verify ordered thermal/hydraulic duty, complete input, sensor/alarm functions and agreed fault states at the selected circuit conditions. Current price, lead time and independently measured efficiency are unknown.

Facility circuit

Provide actual heat-sink fluid, temperatures, pressure and treatment responsibility.

Server circuit

Specify OEM coolant quality, flow and pressure limits plus manifold resistance.

Controls and service

Confirm ordered pumps/filter/sensors, protection thresholds and isolation procedures.

Sources and review scope

Compiled by HVACDeck Editorial. Source review identifies what the publication states; it is not an independent performance test or certification.

  1. Official in-row CDUChecked 2026-10-11 · Full construction/features and original cabinet rendering reviewed; relative flow and available options distinguished from selected ratings.

Editorial method and corrections · Report a detail with this page URL

Turn the evidence into an enquiry

Send the manufacturer your required duty, installation conditions and the unresolved items identified in this brief.

Other equipment from this manufacturer

Envicool MC power-container cooling · Heating, humidity and dry contacts

Envicool BattCool-AC container cooling · Air paths and standby control

Envicool BattCool-C / EMW chillers · Battery coolant and fault duty

Envicool EMA cabinet air conditioners · Air path and filter service

Envicool HC combo cabinet cooling · Heat-pipe and compressor modes

Envicool DC / EC outdoor cabinet cooling · Power and selected duty